Soji-sj900-6-10kva

● High frequency and true double-conversion
● DSP digital control technology
● Input power factor correction (PFC)
● Wide input voltage range (110V-300V)
● Output power factor 0.9
● Cold start
● Frequency adaptive
● ECO mode operation for energy saving
● Selectable output voltage via LCD
● 50Hz/60Hz frequency converter mode available
● Selectable battery low voltage via LCD

● Automatically diagnose when starts

● Advanced battery management (ABM)
● Short circuit and overload protection
● Automatically charging battery at UPS off mode
● Fan speed auto control when load varies
● Standard RS232 communication port
● Optional USB/SNMP communication port
● Optional emergency power off (EPO)
● Optional extension battery bank
● Optional built-in isolation transformer
● Optional manual bypass
● Optional N+X redundancy parallel

MODEL

SJ906II

SJ9010II

Capacity

6KVA/5400W

10KVA/9000W

INPUT
Rated Voltage

208V/220V/230V/240VAC

Voltage Range

Half load (110-300±5VAC

Full load (160-300)±5VAC

Frequency

40-70Hz (Auto Sensing)

Power Factor

≥0.99

Bypass Voltage Range

160V~208V/220V/230V/240VAC+32V

OUTPUT
Voltage

208V/220V/230V/240VAC Setting available via LCD

Voltage Regulation

±1%

Frequency

45-55Hz or 55-65Hz(Synchronized range on AC mode);50/60±0.2Hz(battery mode)

Waveform

Pure sine wave

Crest Factor

3:1

Harmonic Distortion

≤2%(Linear load);≤5%(Non-linear load)

Transfer Time

AC mode to battery mode :0ms

Inverter model to bypass mode:0ms

Overload Capability

105%-125%:Transfer to bypass after 3mins;

125%-150%: Transfer to bypass after 30s;

>150%: Transfer to bypass after 100ms

EFFICIENCY
AC Mode

≥92%

Battery Mode

≥91%

ECO Mode

≥98%

BATTERY
DC Voltage

192V

Inbuilt Battery of Standard Model

16*7Ah

16*9Ah

Charge Current Standard Model

1A

Long Time Model

1A/3A/5A/8A

Typical Recharge Time

8 hours recover to 90% capacity

ALARM
Utility Failure

Beep/4s

Battery Low

Beep/1s

Overload

Beep Twice/1s

UPS Fault

Long Beep

ENVIRONMENT
Humidity

20~90% RH @ 0~40℃(non-condensing)

Noise Level

≤55dB (1m)

MANAGEMENT
Standard RS-232 ,Optional USB

Supports Windows 98/2000/2003/XP/Vista/2008/Windows7/8

Optional SNMP

Power management from SNMP manager and web browser

PHYSICAL
imension(mm) W*D*H

262*514*455(H),262*514*735(S)

Packing Dimension(mm) W*D*H

365*605*610(H),390*625*973(S)

Net Weight(kg)

22.1(H),64.1(S)

22.8(H),70.8(S)

Gross Weight(kg)

25.2(H),72.2(S)

25.9(H),78.9(S)

* Derate capacity to 70% in CUCF mode and to 90% when the output voltage is adjusted to 208VAC.

* S means standard model, H means long backup time model.

SJ900II 6-10KVA user manual
SJ900II 6-10KVA Datasheets