TECHNICAL SPECIFICATION
Unit Static Frequency Converter 50Hz, 60Hz, 400Hz
INPUT
Nominal voltage 400/415VAC 3Ph
Voltage tolerance ± 15%
Nominal frequency 50Hz , 60Hz  and 400Hz ±5%
Current harmonics < 3% at full load (sinusoidal)
OUTPUT
Voltage 200V/400V/415VAC 3-Phase

or 230V/240VAC 1-phase

Frequency 50Hz/ 60Hz/ 400Hz ± 1%
Waveform Sinusoidal
Overall Efficiency 87% – 95%
Max crest max 3 : 1
RECTIFIER
AC Voltage Range -25% – +10%
Efficiency 93% – 97%
Input Frequency Deviation ± 5%
Overload capacity 120% continuous
Current walk in 5 seconds to maximum
Overall current limits 120%
INVERTER
Static regulation 0 -100% load ±1%
Dynamic regulation 100% ±5%, recovering to 1% within 40 millisecond
Total harmonic distortion < 3% linear load
Overload 120% for 60s, 150% for 5s, 200% for 2s
Frequency stability ±0.01% Crystal controlled
Load power factor 0.7 – 1
Efficiency 93% – 98%
ENVIRONMENTAL CONDITIONS
Temperature range at sea level 0 – 400C (full load)

300C at 2000m (full load)

HUMIDITY
Recommended 40% – 60%
Extreme 90%
Noise level < 65dbA at 1meter
Altitude Up to 2500m
COMMUNICATIONS
Ethernet connection Standard with NetAgent
CAN (with Remote Panel) Optional
Power rating 10kW – 15kW – 20kW – 25kW – 30kW – 40kW – 50kW – 60kW – 80kW – 100kW – 120kW – 150kW – 200kW – 250kW – 300kW – 400kW