EA600 1000VA-3000VA Line interactive UPS uses Line Interactive technology and provides a sinusoidal output with power factor 0.8. It ensures a high level of protection against mains power disturbances. When the mains power supply fails, it powers sensitive equipment with a perfectly sinusoidal supply for maximum power continuity and reliability. It is the ideal solution for the protection of peripheral network devices, servers, and network backup systems
● Pure sine wave output
● Output power factor 0.8
● DSP digital control
● Boost and buck AVR for voltage stabilization
● Auto sensing frequency
● Adjustable charging current and battery shutdown point
● Settable ECO mode and no-load shutdown
● Humanized alarm system
● Power-on self test
● Cold start
● Auto restart when mains power is restored
● Intelligent battery management
● Short circuit and overload protection
● Automatic charging at UPS OFF mode
● USB & RJ45, AS400/SNMP (optional) communication port
MODEL |
EA610 |
EA615 |
EA620 |
EA630 |
|||
Capacity |
1000VA/800W |
1500VA/1200W |
2000VA/1600W |
3000VA/2400W |
|||
INPUT | |||||||
AC voltage |
100V/110V/120Vac ±26% or 220V/230V240Vac ±26% (-35% optional) |
||||||
Frequency |
50Hz/60Hz ±10% (auto-sense) |
||||||
OUTPUT | |||||||
Voltage during battery operation |
100V/110V/120Vac ±5% or 220V/230V/240Vac ±5% |
||||||
Voltage during mains operation |
100V/110V/120Vac ±9% or 220V/230V240Vac ±9% |
||||||
Frequency |
50/60Hz±0.3Hz (auto-sense & settable) |
||||||
Waveform |
Pure sine wave |
||||||
Harmonic distortion |
≤5%(linear load) |
||||||
Transfer time |
≤ 8ms |
||||||
ECO mode |
Settable(<3% load) to enter after 80s |
||||||
No-load shutdown |
Settable (<3% load) shutdown after 80s |
||||||
EFFICIENCY | |||||||
AC mode |
Max 98% |
||||||
Battery mode |
Max 85% (linear load) |
||||||
BATTERIES | |||||||
Standard model | DC voltage |
24V |
24V |
36V |
48V |
||
Number & type |
2 x 12V7Ah |
2 x 12V9Ah |
3 x 12V9Ah |
4 x 12V9Ah |
|||
Charge current |
Standard model: 1A (default), 0-5A (adjustable by back-end setting) |
||||||
Typical recharge time |
8 h |
||||||
End of discharge voltage |
Single battery 10.2Vdc (default), 9.6-11.5Vdc (adjustable) |
||||||
ALARM | |||||||
Battery mode |
Beep every 5s, be silent in 60s |
||||||
Low Battery |
Keep beeping for 0.16s at interval of 0.16s (quick beep) |
||||||
Overload |
Keep beeping for 2s at interval of 0.5s (long beep) |
||||||
COMMUNICATIONS | |||||||
USB+RJ45 |
Supports Windows 98/2000/2003/XP/Vista/2008/7/8/10 |
||||||
SNMP (option) |
Power management from SNMP manager and web browser(standard with slot) |
||||||
OTHERS | |||||||
Protections |
Overload- short circuit- battery overcharge- overdischarge |
||||||
Humidity |
10~90% RH @ 0~40℃ (non-condensing) |
||||||
Noise level |
≤5dB (1m) |
||||||
PHYSICAL | |||||||
Tower | Dimension(mm) W*D*H |
144 x 346.5 x 215 |
144 x 411.5 x 215 |
190 x 467 x 335.5 |
|||
Packing Dimension(mm) W*D*H |
236 x 427 x 316 |
236 x 492 x 316 |
320 x 592 x 462 |
||||
Net Weight(kg) |
12.2 |
14.2 |
18.5 |
28.1 |
|||
Gross Weight(kg) |
13.2 |
15.2 |
19.8 |
30.2 |
|||
Rack Mount | Dimension(mm) W*D*H |
440 x 338 x 88 |
440*410*132 |
||||
Packing Dimension(mm) W*D*H |
448 x 611 x 208 |
505*611*235 |
|||||
Net Weight(kg) |
14.6 |
17.2 |
21.3 |
26.7 |
|||
Gross Weight(kg) |
16.8 |
20.4 |
24.5 |
30.5 |